Compact equipment assembly for distribution substations (CEADS)
1Key Takeaways
This European Standard specifies the service conditions, rated characteristics, general structural requirements and test methods of the prefabricated assembly of the main electrical functional units of a HV/LV Distribution Substation, duly interconnected, for alternating current of rated operating voltages above 1 k…
2Scope / Description
This European Standard specifies the service conditions, rated characteristics, general structural
requirements and test methods of the prefabricated assembly of the main electrical functional units of a
HV/LV Distribution Substation, duly interconnected, for alternating current of rated operating voltages
above 1 kV and up to and including 52 kV on the HV side, service frequency 50 Hz. This assembly is to
be cable-connected to the network.
This Compact Equipment Assembly for Distribution Substation (CEADS) as defined in this standard is
designed and tested to be a single product with a single serial number and one set of documentation.
Such equipment is delivered as single transport unit. For practical reasons manufacturer and user can
agree to transport the unit dismantled if transport or installation of the complete CEADS is not possible. In
that case suitable verification tests shall be carried out at the installation site.
A CEADS is not a Distribution Substation, either prefabricated (covered by EN 62271-202) or not
(covered by EN 61936-1). However CEADS is intended to become part of a Distribution Substation
assembling the HV equipment, the power transformer and the LV equipment duly interconnected (see
Annex C, which also explains the origin and types of CEADS).
The functions of a CEADS are:
– switching and control for the operation of the HV side and protection of the HV/LV transformer
functional unit;
– HV/LV transformation;
– switching and control for the operation and protection of the LV feeders.
However relevant provisions of this standard are also applicable to designs where not all of these
functions exist (e.g. equipment comprising only HV/LV transformation and switching and control for the
operation and protection of the LV feeder functions).
For public distribution networks, CEADS are intended for installation within an indoor or outdoor closed
electrical operating area (see Definition 1.3.3) forming part of a Distribution Substation.
For industrial applications, such as factories, installation of CEADS outside a closed electrical operating
area may be allowed provided that safety regulations are fulfilled by additional measures adopted at the
installation site under the responsibility of the designer of the installation.
This standard considers the potential interaction between the individual functions when closely installed
and interconnected to form a type tested assembly and defines ratings, particular design and construction
requirements and test procedures for this assembly.