JGJ/T 46-2024
CJ · 2024-10-17

Technical standards for temporary power safety at construction sites of buildings and municipal engineering projects

规范 Cited by 1

1Key Takeaways

Now approved, the "Safety Technical Standard for Temporary Electrical Use at Construction and Municipal Engineering Sites" is established as an industry standard, numbered JGJ/T46-2024, to be implemented starting January 1, 2025. The original industry standard "Technical Specifications for Safety of Temporary Electrica…

2Expert Interpretation

Comprehensively analyze the core contents of "Technical Standard for Temporary Electricity Safety at Construction Sites of Buildings and Municipal Engineering" JGJ/T46-2024, covering TN-S system configuration, residual current protection settings, three-level distribution specifications and distribution device selection requirements, and provide implementation points and typical application scenario analysis.

Standard Revision Background and Technical Evolution

This standard replaces the JGJ46-2005 version. The main revisions include: expanding the "grounding and lightning protection" chapter to "distribution system", adding special provisions for residual current protection, refining the technical requirements for wire rope wiring, and supplementing the requirements for tower crane power cable laying. The revision reflects three major trends: strengthening system protection, refining equipment specifications, and improving management requirements.


Core safety technology system

System typeConfiguration requirementsKey parameters
TN-S system When a dedicated transformer is used for power supply, the PE line is drawn from the N line on the power supply side PE line cross section ≥ 50% of the phase line
Secondary residual current protection Main distribution box>30mA/0.1s, switch box ≤30mA/0.1s Product ≤30mA·s
Three-level distribution Main distribution box→distribution box→switch box, spacing ≤30m Switch box is ≤3m away from equipment

Key technical requirements for distribution devices

Typical violation case: A construction site used aluminum core wire as PE wire, resulting in grounding failure. According to the standard, the following should be selected:

  • Distribution device PE wire: ≥2.5mm² insulated multi-strand soft copper wire
  • Handheld tool PE wire: ≥1.5mm² insulated multi-strand soft copper wire
  • It is prohibited to install switches/fuses on PE wire

Distribution box steel plate thickness requirements: switch box ≥1.2mm, distribution box ≥1.5mm, fixed installation height 1.4-1.6m.


Protection measures for special places

Type of placeVoltage limitProtection requirements
Tunnel/civil air defense project ≤36V Dual-winding safety isolation transformer
Inside metal container ≤12V Class III tools + residual current protection
Tower crane 380V Repeated grounding + lightning protection grounding (R≤10Ω)

Implementation suggestions and common problems

Main points for cable laying: Direct burial depth ≥ 0.7m, 50mm fine sand + protective plate on the top and bottom of the cable, parallel distance with the pipe network ≥ 2m. Overhead line spacing ≤ 35m, number of joints ≤ 50%.

Typical problem handling: When the distance to the external power line does not meet the requirements of Table 8.1.2, insulation isolation protection (reaching IP30 level) or negotiated power outage migration should be adopted.

3Version History

JGJ/T 46-2024 2024-10-17

5Citation Network

1
Cite this standard
0
Referenced herein

6Frequently Asked Questions

What is JGJ/T 46-2024?
JGJ/T 46-2024 — Technical standards for temporary power safety at construction sites of buildings and municipal engineering projects is an international standard developed by Professional Standard - Urban Construction. Now approved, the "Safety Technical Standard for Temporary Electrical Use at Construction and Municipal Engineering Sites" is established as an industry standard, numbered JGJ/T46-2024, to be implemented starting January 1, 2025. The original...
What does JGJ/T 46-2024 cover?
This standard covers: Now approved, the "Safety Technical Standard for Temporary Electrical Use at Construction and Municipal Engineering Sites" is established as an industry standard, numbered JGJ/T46-2024, to be implemented starting January 1, 2025. The original industry standard "Technical Specifications for Safety...
Who should use this standard?
This standard is intended for organizations, professionals, and stakeholders involved in various industries and sectors. It is applicable to manufacturers, service providers, regulatory bodies, and certification organizations.
What is the latest version of JGJ/T 46-2024?
The current published version is JGJ/T 46-2024, published on 2024-10-17. Always check for amendments or pending revisions.
How do I purchase JGJ/T 46-2024?
You can purchase JGJ/T 46-2024 by visiting our contact page. Click "Get This Standard" to view pricing and send a purchase inquiry. Our team will respond with payment and delivery details.